PM modular series - PMA model

PMA series energy storage converter adopts modular design, it supports power module independent operation and parallel operation, it has flexible system configuration, easy to use, suitable for on-grid small-scale industrial and commercial.

Highly efficient and intelligent

Leading three-level space vector modulation SVPWM with wide voltage range charging and discharging for parallel operation of multiple machines. Leading midpoint balance technology, with DC component adjustment and low-frequency pulse current in the bypass bus, can prolong battery life and improve unbalanced and nonlinear adaptability.

Safe and reliable

Intelligent electrical protection with fault isolation and fast breaking.
Multiple safety protection with SPD ISO GFCI monitoring function and intelligent electrical protection linkage.

Simple and flexible

Standard power capacity modules are adapted to standard energy storage cell clusters.
19-inch 3U standard size design, support horizontal/vertical installation.

Application

Peak Load Shifting
Demand Side Management
Emergency Power Supply
Dynamic Expansion

PM modular series - PMA model

Модульна серія PM - модель PMA
Model PMA080 PMA0105 PMA0125
DC(battery)
Max. DC power (kW) 96 126 150
DC voltage range (V) 615~950Vdc(3W+PE)/650~950Vdc(3W+N+PE)
DC full load voltage range (V) 650~950Vdc(3W+PE)/680~950Vdc(3W+N+PE)
Max. DC current (A) ±150 ±195 ±230
Voltage stabilization accuracy ±1%
Current stabilization accuracy ±2%
AC(on-grid)
Rated AC power (kW) 80 105 125
Max. AC power (kWA) 96 126 150
Voltage scale 3W+PE or 3W+N+PE
Rated voltage (V) 400
Rated AC current (A) 115 150 180
Max. AC current (A) 138 180 216
THDi <2%
Allowable grid voltage range (V) 400Vac±15%
Allowable grid frequency range (Hz) 50±2Hz/60±2Hz
Power factor adjustment range -1~+1
AC( off-grid)
Rated AC power (kW) 80 105 125
Max. output current (A) 138 180 216
Max. AC power (kWA) 96 126 150
Rated voltage (V) 230/400
Rated frequency (Hz) 50Hz/60Hz
Voltage accuracy ±1%
Frequency accuracy (50Hz/60Hz ±0.1%)Hz
THDV 3% (linear load)
Unbalanced load capacity Supports 100% single-phase unbalance
Overload capacity ≤110%,continuous ;≤120%,2min ;>120%,200ms
System
Max. efficiency 98.7%
Charge/Discharge switching time (ms) <20
Ingress protection IP20 (power compartment) IP6X (control compartment)
Relative humidity <95%(non-condensing)
Operating temperature range (℃) -30~+60 (>45 derating)
Max. operating altitude (m) 5000(>3000 derating)
Communication interface RS485/CAN/Ethernet
BMS/EMS access Support
Dimension W*D*H (mm) 483*680*174 19inch 4U
483*680*220 19inch 5U
483*680*174 19inch 4U
483*680*220 19inch 5U
584*680*174 23inch 4U 584*680*220 23inch 5U
Weight (kg) 48(back wiring)
50(front wiring)
48(back wiring)
50(front wiring)
58(back wiring)
60(front wiring)
Модульна серія PM - модель PMA
Model PMA060 PMA0100
DC(battery)
Max. DC power (kW) 75 126
DC voltage range (V) 700~950(720~900 full load)
Max. DC current (A) ±110 ±180
Voltage stabilization accuracy ±1%
Current stabilization accuracy ±2%
AC(on-grid)
Rated AC power (kW) 62.5 105
Max. AC power (kW) 75 126
Voltage scale 3W+PE
Rated voltage (V) 480
Rated AC current (A) 75 126
Max. AC current (A) 90 150
THDi <3%
Allowable grid voltage range (V) 480±15%
Allowable grid frequency range (Hz) 60/50±2.5
Power factor adjustment range -1~+1
Active power accuracy 1%
Reactive power accuracy 2%
System
Max. efficiency 98.5% 98.7%
Charge/Discharge switching time (ms) <20
Protection degree IP20
Relative humidity <95% (Non-condensing)
Operating temperature range -30~60 (derating over 45℃)
Max. operating altitude 5,000m(>3,000m Derating)
Communication interface RS485/CAN/Ethernet
BMS/EMS access Yes
Dimensions (W*D*H)(mm) 440*550*133
Weight(Kg) 30 40